Size a TONGYI HEMS-optimised R290 air-to-water heat pump for a European home — heating plus hot water. Pick your city from the built-in table (187 cities, each with a sourced design temperature) or type the design temperature yourself. All figures come from the manufacturer's datasheet, interpolated between test points — never extrapolated.
Interpolated at your design point from the datasheet (Technical reference, bottom of page), then reduced by the 5% defrost allowance below.
© 2026 Guangdong Tongyi Heat Pump Science and Technology Co., Ltd. — sizing results are TONGYI reference material; please contact TONGYI rather than republishing them.
—
| Model | Capacity | COP | Coverage | SCOP | Est. electricity |
|---|
Coverage = capacity after the 5% defrost allowance ÷ design heat load; the pre-allowance figure is under each capacity. SCOP is the datasheet average-climate value at your flow temperature — published at 35 °C and 55 °C only, so 45 °C and 75 °C show “—”.
No single unit reaches the target at this design point, so identical units of one model share the load in parallel. Total capacity = units × unit capacity after the 5% defrost allowance; COP is unchanged.
| Model (cascade of identical units) | Units needed | Total capacity | Coverage | Total max. input power | Total net weight |
|---|
Optional. What heats the home today becomes the basis for the running-cost and CO₂ comparison. Leave the annual use empty and the CO₂ section keeps its generic gas / oil / direct-electric baselines.
Default for the selected source; edit it if you know the real figure.
From last year's bills. Rough conversions: oil litres × 10 kWh/litre; gas m³ × 10.5 kWh/m³.
Per kWh of fuel: gas 0.202, oil 0.266, LPG 0.227. District heating default 0.200 (editable). Direct electric and old heat pumps use the grid intensity from the CO₂ section (default 0.233).
Both prices are editable starting values — set them to the household's actual tariffs.
Optional. Know the old unit's rated capacity and design temperatures? The tool estimates the design heat load from it — reference estimate only; final sizing still needs EN 12831.
From the old unit's nameplate or manual. Leave empty if unknown.
The condition at which the rated capacity above was measured / stated.
Defaults to the site design temperature; for a heat pump it follows the rated condition above (A7 = 7 °C, A2 = 2 °C, A−7 = −7 °C). For a boiler, the outdoor temperature it was sized for.
Picking a preset fills the flow / return fields below; you can still edit them.
Copies the estimate into the design-load override in the form, marked reference-derived, so you can see the recommended model change. It does not turn the estimate into an EN 12831 load.
An estimate, not a measurement: the recommended heat pump vs gas, oil and direct electric heating delivering the same annual heat, using the factors shown in the result. Refrigerant leakage excluded (R290 GWP 0.02).
Default 0.233 kg CO₂/kWh — EU average. Edit for the local grid.
HEMS-optimised R290 smart heat pump — heating, cooling and DHW, plate heat exchanger (Danfoss), twin-rotary DC inverter compressor (peak COP 5.0), Welling fan, SHIMGE variable-frequency pump, built-in WiFi and EEBUS. CE (LVD / EMC / RED), ErP, SG Ready; listed for SEAI and BAFA subsidies (eligibility and amounts under each national scheme follow the rules in force at the time of application — position as of November 2026); Huawei FusionSolar PV linkage.
| Parameter | TAHMV7 R | TAHMV10 R | TAHMV12S R | TAHMV20S R |
|---|---|---|---|---|
| ErP class, average climate (35 °C / 55 °C) | A+++ / A++ | A+++ / A++ | A+++ / A++ | A+++ / A++ |
| SCOP, average climate (35 °C / 55 °C) | 4.60 / 3.55 | 4.56 / 3.62 | 4.80 / 3.55 | 4.90 / 3.65 |
| Seasonal space heating efficiency ηs (35 °C / 55 °C) | 181% / 139% | 179% / 142% | 189% / 139% | 193% / 143% |
| ErP test report | CN25EQFS 001 | CN25LVRB 001 | CN25LYL1 001 | CN25QDAB 001 |
| Power supply | 220–240 V · 1 Ph · 50 Hz | 220–240 V · 1 Ph · 50 Hz | 380–415 V · 3 Ph · 50 Hz | 380–415 V · 3 Ph · 50 Hz |
| Max. input power / current | 2.8 kW / 12.7 A | 4.3 kW / 19.1 A | 5.2 kW / 8.5 A | 7.6 kW / 13.4 A |
| Compressor (DC inverter) | Highly WHP07600PSDPC9KQ | Panasonic H420D7KZAAC6 | Panasonic H550D7VZAAC6 | Panasonic H800D7JZAAC6 |
| Refrigerant / charge (GWP 0.02) | R290 · 0.75 kg | R290 · 0.9 kg | R290 · 1.1 kg | R290 · 1.5 kg |
| Rated water flow | 1.2 m³/h | 1.77 m³/h | 2.06 m³/h | 3.44 m³/h |
| Sound power level | 52.1 dB(A) | 51.7 dB(A) | 53.6 dB(A) | 61.1 dB(A) |
| Sound pressure, 1 m / 10 m | 38 / 18 dB(A) | 37.6 / 18 dB(A) | 39.4 / 20 dB(A) | 46.2 / 26 dB(A) |
| Dimensions L × W × H | 1288 × 514 × 888 mm | 1288 × 514 × 888 mm | 1288 × 514 × 888 mm | 1288 × 514 × 1397 mm |
| Net weight | 121 kg | 125 kg | 153 kg | 220 kg |
| Operating range | Ambient −25 to +46 °C · heating −25 to +46 °C · cooling +18 to +46 °C · heating outlet water 30–75 °C · cooling outlet water 7–22 °C · max. outlet water 75 °C | |||
Exactly as published in the datasheet, including its non-monotonic values. “—” means the datasheet publishes no value at that point. The calculator interpolates linearly between these points.
| Condition | TAHMV7 R | TAHMV10 R | TAHMV12S R | TAHMV20S R |
|---|
Cooling: capacity (W) · EER at A35. DHW: heating capacity (W) · COP. DHW figures below +7 °C ambient are published for the TAHMV20S R only.
| Condition | TAHMV7 R | TAHMV10 R | TAHMV12S R | TAHMV20S R |
|---|
This follows the mainstream European approach: a rule-of-thumb or EN 12831 heat load, selection at the design point rather than at nameplate conditions, and seasonal efficiency from the ErP SCOP — the pattern used across mainstream European sizing guides.
Data source. All performance data in this reference section is taken from the TONGYI datasheet file R290_specification_datasheet_20261106.xlsx, dated 2026-11-06 (HEMS-optimised R290 smart heat pump series TAHMV7 R / TAHMV10 R / TAHMV12S R / TAHMV20S R). Values are reproduced as published, including the datasheet's few non-monotonic figures; where the datasheet has no value, this page shows “—”. Interpolated figures are calculated by this tool from those published points and are marked as interpolated.
Climate data. Built-in design temperatures are reproduced from the source named next to each value (national annexes, standards and references as cited there; first researched 2026-11-16, table expanded 2026-11-18); where sources conflict — Berlin, Munich, Brussels, Amsterdam, Stockholm, Suwałki, Budapest — the conflict is stated next to the value and the applied figure is identified. Heating degree days are from ECOFYS Annex 1, Table 12 (Eurostat method: base 18 °C, threshold 15 °C; Meteonorm long-term averages). This page performs no online location lookup and sends no data anywhere: places outside the built-in table are covered by entering the design temperature manually.
Leave your details and email this sizing to TONGYI at info@tongyiheatpump.com — the button opens your own email app with the form and the sizing summary already filled in, and TONGYI can then contact you back.
Nothing is sent until you click the button and send the email from your own email app — your details are not stored or transmitted by this page.