TONGYI your trusted global heat pump solution partner

TONGYI R290 Heat Pump Sizing Tool

Size a TONGYI HEMS-optimised R290 air-to-water heat pump for a European home — heating plus hot water. Pick your city from the built-in table (187 cities, each with a sourced design temperature) or type the design temperature yourself. All figures come from the manufacturer's datasheet, interpolated between test points — never extrapolated.

TAHMV7 R · 1-phase TAHMV10 R · 1-phase TAHMV12S R · 3-phase TAHMV20S R · 3-phase R290 · GWP 0.02 · max. outlet 75 °C

Your building

Results update as you type.

Site location

Pick a city and its sourced design temperature fills in below. Anywhere else, type the design temperature from the national annex — everything runs offline in your browser, and the value below stays editable either way.

Heated floor area
m²
Building class (rule of thumb)

Rule-of-thumb classes from European sizing guides — a starting estimate; EN 12831 governs the final design.

kW
Design outdoor temperature −7 °C

From the city table above, or set manually from the national annex. Below −20 °C the datasheet has no test points, so the tool states no capacity rather than extrapolating.

Heating flow temperature
Domestic hot water

Demand at 50 °C draw-off; energy is calculated on a 10 → 55 °C rise.

Operation mode
Annual heat demand (optional)
kWh/yr

If entered, estimated annual electricity = annual heat demand ÷ SCOP at the selected flow temperature.

See your recommended size ↓

Result Recommended size

Interpolated at your design point from the datasheet (Technical reference, bottom of page), then reduced by the 5% defrost allowance below.

Design heat load
—
—
DHW energy
—
—
Recommended model
—
—
Backup heater
—
—

© 2026 Guangdong Tongyi Heat Pump Science and Technology Co., Ltd. — sizing results are TONGYI reference material; please contact TONGYI rather than republishing them.

Compare All four models at your design point

—

Model Capacity COP Coverage SCOP

Coverage = capacity after the 5% defrost allowance ÷ design heat load; the pre-allowance figure is under each capacity. SCOP is the datasheet average-climate value at your flow temperature — published at 35 °C and 55 °C only, so 45 °C and 75 °C show “—”.

Existing Existing heating system

Optional. What heats the home today becomes the basis for the running-cost and CO₂ comparison. Leave the annual use empty and the CO₂ section keeps its generic gas / oil / direct-electric baselines.

%

Default for the selected source; edit it if you know the real figure.

kWh/yr

From last year's bills. Rough conversions: oil litres × 10 kWh/litre; gas m³ × 10.5 kWh/m³.

kg CO₂/kWh

Per kWh of fuel: gas 0.202, oil 0.266, LPG 0.227. District heating default 0.200 (editable). Direct electric and old heat pumps use the grid intensity from the CO₂ section (default 0.233).

€/kWh
€/kWh

Both prices are editable starting values — set them to the household's actual tariffs.

Old unit capacity & temperatures — sizing reference

Optional. Know the old unit's rated capacity and design temperatures? The tool estimates the design heat load from it — reference estimate only; final sizing still needs EN 12831.

kW

From the old unit's nameplate or manual. Leave empty if unknown.

The condition at which the rated capacity above was measured / stated.

°C

Defaults to the site design temperature; for a heat pump it follows the rated condition above (A7 = 7 °C, A2 = 2 °C, A−7 = −7 °C). For a boiler, the outdoor temperature it was sized for.

Picking a preset fills the flow / return fields below; you can still edit them.

°C
°C

Copies the estimate into the design-load override in the form, marked reference-derived, so you can see the recommended model change. It does not turn the estimate into an EN 12831 load.

CO₂ Estimated CO₂ reduction

An estimate, not a measurement: the recommended heat pump vs gas, oil and direct electric heating delivering the same annual heat, using the factors shown in the result. Refrigerant leakage excluded (R290 GWP 0.02).

kg CO₂/kWh

Default 0.233 kg CO₂/kWh — EU average. Edit for the local grid.

Read first Limits of this tool

  • Indicative only. Final sizing must be a room-by-room EN 12831 heat-loss calculation by a qualified installer. The W/m² classes here are rules of thumb, not a substitute.
  • Check the design temperature. Confirm it against the national annex for the actual site — it drives the whole selection. Altitude and exposure can shift it by several degrees (France and Italy correct by about 1 K per 100 m; the UK by 0.6 K per 100 m), and a 1 K error changes the design load by roughly 3–5%.
  • Check the electrical supply. TAHMV7 R and TAHMV10 R are single-phase (220–240 V); TAHMV12S R and TAHMV20S R need three-phase (380–415 V). Confirm what the property has before specifying.
  • Efficiency collapses at the extremes. At A−20/W55 the datasheet COP is 0.95–1.30 across the range. In cold climates at high flow temperatures a backup heater is not optional — plan for it.
  • Published values, no extrapolation. Datasheet figures — including a few non-monotonic ones (the TAHMV10 R delivers more at A7/W55, 11,097 W, than at A7/W45, 10,885 W) — are used exactly as published. The lowest test point is −20 °C, so below that the tool states no capacity.
  • Definitions differ by country. German and French values are coldest 2-day means; UK values are 99% hourly figures; Polish and Romanian values are statutory climate zones; ASHRAE proxies are 99.6% hourly percentiles. The badge with each applied value states its definition — an ASHRAE proxy is not an EN 12831 design temperature.
  • Defrost allowance −5%. Every capacity used for selection — single unit and cascade alike — is the interpolated datasheet capacity reduced by 5% for defrost cycles: a conservative engineering allowance chosen by TONGYI, not a datasheet value. The result shows both the capacity before the allowance and the reduced capacity actually used.
Technical reference(技术参考)— datasheet, sizing method and data sources

Datasheet Model specification

HEMS-optimised R290 smart heat pump — heating, cooling and DHW, plate heat exchanger (Danfoss), twin-rotary DC inverter compressor (peak COP 5.0), Welling fan, SHIMGE variable-frequency pump, built-in WiFi and EEBUS. CE (LVD / EMC / RED), ErP, SG Ready; listed for SEAI and BAFA subsidies (eligibility and amounts under each national scheme follow the rules in force at the time of application — position as of November 2026); Huawei FusionSolar PV linkage.

ParameterTAHMV7 RTAHMV10 RTAHMV12S RTAHMV20S R
ErP class, average climate (35 °C / 55 °C)A+++ / A++A+++ / A++A+++ / A++A+++ / A++
SCOP, average climate (35 °C / 55 °C)4.60 / 3.554.56 / 3.624.80 / 3.554.90 / 3.65
Seasonal space heating efficiency ηs (35 °C / 55 °C)181% / 139%179% / 142%189% / 139%193% / 143%
ErP test reportCN25EQFS 001CN25LVRB 001CN25LYL1 001CN25QDAB 001
Power supply220–240 V · 1 Ph · 50 Hz220–240 V · 1 Ph · 50 Hz380–415 V · 3 Ph · 50 Hz380–415 V · 3 Ph · 50 Hz
Max. input power / current2.8 kW / 12.7 A4.3 kW / 19.1 A5.2 kW / 8.5 A7.6 kW / 13.4 A
Compressor (DC inverter)Highly WHP07600PSDPC9KQPanasonic H420D7KZAAC6Panasonic H550D7VZAAC6Panasonic H800D7JZAAC6
Refrigerant / charge (GWP 0.02)R290 · 0.75 kgR290 · 0.9 kgR290 · 1.1 kgR290 · 1.5 kg
Rated water flow1.2 m³/h1.77 m³/h2.06 m³/h3.44 m³/h
Sound power level52.1 dB(A)51.7 dB(A)53.6 dB(A)61.1 dB(A)
Sound pressure, 1 m / 10 m38 / 18 dB(A)37.6 / 18 dB(A)39.4 / 20 dB(A)46.2 / 26 dB(A)
Dimensions L × W × H1288 × 514 × 888 mm1288 × 514 × 888 mm1288 × 514 × 888 mm1288 × 514 × 1397 mm
Net weight121 kg125 kg153 kg220 kg
Operating rangeAmbient −25 to +46 °C · heating −25 to +46 °C · cooling +18 to +46 °C · heating outlet water 30–75 °C · cooling outlet water 7–22 °C · max. outlet water 75 °C

Datasheet Heating test points — capacity (W) · COP

Exactly as published in the datasheet, including its non-monotonic values. “—” means the datasheet publishes no value at that point. The calculator interpolates linearly between these points.

ConditionTAHMV7 RTAHMV10 RTAHMV12S RTAHMV20S R

Datasheet Cooling and DHW test points

Cooling: capacity (W) · EER at A35. DHW: heating capacity (W) · COP. DHW figures below +7 °C ambient are published for the TAHMV20S R only.

ConditionTAHMV7 RTAHMV10 RTAHMV12S RTAHMV20S R

Method How sizing works

This follows the mainstream European approach: a rule-of-thumb or EN 12831 heat load, selection at the design point rather than at nameplate conditions, and seasonal efficiency from the ErP SCOP — the pattern used across mainstream European sizing guides.

  1. Location. The built-in city table (187 cities, expanded November 2026) is the only location source — the same pattern as mainstream European postcode and climatic-location tables, none of which takes the statutory design value from a live weather API. Each built-in value carries a badge: verified table or zone value, national practice value, secondary source, or ASHRAE proxy (a 99.6% hourly percentile, not an EN 12831 value). A place outside the table is not looked up online: enter its design temperature manually from the national annex for the site. A few places are still deliberately absent rather than filled with guesses — Newcastle among them, and most smaller towns everywhere; the manual entry covers them.
  2. Design heat load. Either floor area × a W/m² class (new passive 35, new / good renovation 50, post-2000 70, 1980–2000 80, old uninsulated 100, very old 120 W/m²), or your own EN 12831 result in kW, which overrides the estimate. EN 12831 — a room-by-room calculation of fabric and ventilation losses at the design temperature — is the final method; the W/m² figure only gets you to a first selection.
  3. Select at the design point, not the badge. A heat pump's output falls as the outdoor temperature drops and as the flow temperature rises. What matters is the capacity at your design outdoor temperature and your flow temperature — e.g. A−7/W35 — not the headline kilowatt rating.
  4. Interpolation only. Capacity and COP at the design point are interpolated linearly between the nearest published datasheet test points (ambient 7, 2, −7, −15, −20 °C; flow 35, 45, 55 °C). Nothing is extrapolated: below −20 °C, and at 75 °C flow away from the A7/A2 test points, the tool states no value rather than guessing one. Lower flow temperatures always win — the same unit delivers more heat, more efficiently, at W35 than at W55.
  5. Defrost allowance −5%. The interpolated capacity is then reduced by 5% before any selection, coverage or cascade calculation uses it. The 5% is a conservative engineering allowance for defrost losses, chosen by TONGYI — it is not a datasheet figure, and COP is not reduced. The result area shows both the interpolated capacity and the reduced capacity.
  6. Monovalent or monoenergetic. Monovalent: the heat pump alone covers 100% of the design load. Monoenergetic (mainstream European practice): the heat pump is sized to 70–85% of the design load and an electric backup heater covers the remainder — the unit is smaller and cheaper, runs at full load for most of the season, and the backup only cuts in on the coldest days, which are few. If no model reaches the target, the tool recommends the largest and states the backup size needed.
  7. Cascade above the largest single unit. When the design load — or, in monoenergetic mode, the target load — exceeds what the largest single model (TAHMV20S R) delivers at the design point, the tool recommends a same-capacity cascade instead: N identical units of one model in parallel, with total capacity = N × that model's interpolated capacity at the design point and the COP unchanged. The recommended cascade is the option with the fewest units, then the smallest overshoot above the target, and the cascade table compares all four models (units needed, total capacity, coverage, total maximum input power, total net weight). Cascades are capped at 8 units; beyond that, talk to TONGYI about a larger or commercial solution (info@tongyiheatpump.com). Cascaded units need a common buffer tank and cascade control, and the installer must confirm the hydraulics, the electrical supply and the R290 charge per unit.
  8. Domestic hot water. Daily DHW energy = occupants × litres per person × 1.163 Wh/(L·K) × 45 K (10 → 55 °C). It is shown separately from the space-heating design load; the DHW test points in the datasheet table above give each model's hot-water capacity and COP.
  9. Seasonal running cost. With an annual heat demand entered, estimated annual electricity = annual heat demand ÷ SCOP at the chosen flow temperature, using the datasheet SCOP for average climate. SCOP is published at 35 °C and 55 °C flow only.
  10. Existing heating system comparison. If you enter the existing heat source, its efficiency (or SCOP for an old heat pump), last year's fuel / energy use and your fuel and electricity prices, the tool estimates the old system's delivered heat (use × efficiency), CO₂ (use × the emission factor shown — gas 0.202, oil 0.266, LPG 0.227 kg CO₂/kWh of fuel; grid intensity for direct electric and old heat pumps; an editable 0.200 for district heating) and running cost (use × price), and compares them with the new heat pump at the sizing annual heat demand (demand ÷ SCOP for electricity, × electricity price for cost, × grid intensity for CO₂). Savings are shown in €/yr, kWh/yr and kg CO₂/yr with percentages. If the old system's delivered heat and the sizing demand differ by more than 20%, the tool says so and still compares on the sizing demand.
  11. Old-unit sizing reference. If the old unit's rated heating capacity and its rating condition are entered, the tool estimates the design heat load as rated capacity × (20 − site design outdoor temperature) ÷ (20 − outdoor temperature at rating), using a 20 °C indoor temperature, and shows it as a likely range of 70–100% of that figure — boilers in particular are commonly oversized, so a single figure would overstate the precision. For an old heat pump the proportional adjustment is rough, because heat-pump capacity does not fall linearly with outdoor temperature. The “Use as sizing reference” button copies the estimate into the design-load override and marks it reference-derived; the page then compares the W/m² load, the old-unit range and the load actually used, and warns when the old-unit reference and the W/m² load differ by more than 20%. A flow-temperature check runs alongside: above 55 °C old flow temperature, the same radiators will deliver less heat at 55 °C with the new heat pump, so radiator sizing must be checked and 55 °C is suggested as the new design flow temperature; at 45 °C or below, the existing emitters already suit low-temperature operation. Final sizing still requires a room-by-room EN 12831 calculation.
  12. CO₂ reduction estimate. Where an annual heat demand is available — entered directly, or estimated from the selected built-in city's heating degree days as design load (kW) × HDD × 24 ÷ (20 − design outdoor temperature), plus DHW energy (occupants × litres per day × 45 K × 1.163 Wh/(L·K) × 365 days) — the tool estimates annual CO₂ for the recommended heat pump (heat ÷ SCOP × grid intensity, default EU average 0.233 kg CO₂/kWh, editable) against a gas boiler (0.202 kg CO₂/kWh of fuel at 90% efficiency), an oil boiler (0.266 kg CO₂/kWh of fuel at 85%) and direct electric heating (COP 1.0, same grid intensity). Every factor is shown with the result. It is an estimate only, and refrigerant leakage is not included (R290 GWP 0.02). With neither an entered demand nor a city HDD, the section asks for the annual heat demand rather than guessing.

Data source. All performance data in this reference section is taken from the TONGYI datasheet file R290_specification_datasheet_20261106.xlsx, dated 2026-11-06 (HEMS-optimised R290 smart heat pump series TAHMV7 R / TAHMV10 R / TAHMV12S R / TAHMV20S R). Values are reproduced as published, including the datasheet's few non-monotonic figures; where the datasheet has no value, this page shows “—”. Interpolated figures are calculated by this tool from those published points and are marked as interpolated.

Climate data. Built-in design temperatures are reproduced from the source named next to each value (national annexes, standards and references as cited there; first researched 2026-11-16, table expanded 2026-11-18); where sources conflict — Berlin, Munich, Brussels, Amsterdam, Stockholm, Suwałki, Budapest — the conflict is stated next to the value and the applied figure is identified. Heating degree days are from ECOFYS Annex 1, Table 12 (Eurostat method: base 18 °C, threshold 15 °C; Meteonorm long-term averages). This page performs no online location lookup and sends no data anywhere: places outside the built-in table are covered by entering the design temperature manually.